Table 5: descriptions of large-scale system tests undertaken by the BRE and the number of buildings with similar cladding systems – 31 December 2018
Updated 10 January 2019
Download CSV 1.13 KB
Large-scale system test | ACM cladding category tested | Insulation type tested | Result | Private Buildings | Local authority | Housing association | Publicly-Owned Buildings | Total Buildings |
---|---|---|---|---|---|---|---|---|
1 | Category 3 | Foam Insulation | Fail | 43 | 9 | 30 | 2 | 84 |
2 | Category 3 | Mineral Wool | Fail | 22 | 33 | 49 | 0 | 104 |
3 | Category 2 | PIR foam | Fail | 4 | 1 | 3 | 0 | 8 |
4 | Category 2 | Mineral Wool | Pass | 5 | 1 | 5 | 1 | 12 |
5 | Category 1 | Foam Insulation | Pass | 0 | 0 | 0 | 0 | 0 |
6 | Category 1 | Mineral Wool | Pass | 0 | 0 | 0 | 0 | 0 |
7 | Category 2 | Phenolic Foam | Fail | 9 | 0 | 14 | 0 | 23 |
Na | Category 3 | Not in a systems test | Inferred fail | 54 | 2 | 12 | 5 | 73 |
Na | Category 2 | Not in a systems test | Inferred fail | 18 | 0 | 0 | 2 | 20 |
Na | Category 1 | Not in a systems test | Inferred pass | 0 | 0 | 0 | 0 | 0 |
Subtotal: Total number of buildings failed BRE test | Not set | Not set | Not set | 150 | 45 | 108 | 9 | 312 |
Confirmed by local authorities as having similar ACM cladding systems to those which have failed large-scale system tests | Not set | Not set | Not set | 118 | 1 | 6 | 0 | 125 |
Total number of buildings with unsafe ACM cladding which are unlikely to meet current building regulation | Not set | Not set | Not set | 268 | 46 | 114 | 9 | 437 |
Subtotal: Total number of buildings passed BRE test | Not set | Not set | Not set | 5 | 1 | 5 | 1 | 12 |
Total number of buildings with confirmed ACM | Not set | Not set | Not set | 273 | 47 | 119 | 10 | 449 |